Integration of Wind Systems with SVC and STATCOM during Various Events to Achieve FRT Capability and Voltage Stability: Towards the Reliability of Modern Power Systems

Author:

Mahmoud Mohamed Metwally1ORCID,Salama Hossam S.12,Bajaj Mohit345ORCID,Aly Mohamed M.1,Vokony Istvan2,Bukhari Syed Sabir Hussain6,Wapet Daniel Eutyche Mbadjoun7ORCID,Abdel-Rahim Abdel-Moamen M.8

Affiliation:

1. Electrical Engineering Department, Faculty of Energy Engineering, Aswan University, Aswan 81528, Egypt

2. Department of Electric Power Engineering, Budapest University of Technology and Economics, Budapest 1111, Hungary

3. Department of Electrical Engineering, Graphic Era (Deemed to be University), Dehradun 248002, India

4. Graphic Era Hill University, Dehradun 248002, India

5. Applied Science Research Center, Applied Science Private University, Amman 11931, Jordan

6. School of Electrical and Electronics Engineering, Chung-Ang University, Dongjak-gu, Seoul 06974, Republic of Korea

7. National Advanced School of Engineering, Université de Yaoundé I, Yaoundé, Cameroon

8. Department of Electrical Engineering, Faculty of Energy Engineering, Aswan University, Aswan, Egypt

Abstract

FACTS tools in modern power systems provide a vital solution to the problems of voltage deviation and fault ride-through (FRT) capability in electrical power systems especially during the integration of wind power. Many distinct journals highlight that the wind-driven squirrel cage generator (SCIG) still accounts for around 15% of operating wind generators so far. To enhance voltage stability and FRT capacity, this paper recommends a cost-effective static VAR compensator (SVC) which has a size rating of six MVAR, and this improves the efficiency of the electrical power system. Different events are considered in this study such as high turbulent wind speed, low turbulent wind speed, unsymmetrical faults, and symmetrical faults to validate the suggested option. Moreover, the suggested solution is compared with the static synchronous compensator (STATCOM) and a fixed capacitor to ensure that during the studied wind speed profiles and faults, voltage stability, reactive power consumption, and FRT capability are realized. An overall comparison among them is performed under all studied scenarios to summarize their benefits and impacts. The simulated results show the effectiveness and superiority of SVC in improving the operation of an integrated wind system based on a grid-linked SCIG and the performance of the power system. The modeling of SCIG, SVC, and STATCOM is designed by MATLAB/Simulink toolbox.

Publisher

Hindawi Limited

Subject

Energy Engineering and Power Technology,Fuel Technology,Nuclear Energy and Engineering,Renewable Energy, Sustainability and the Environment

Cited by 8 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3