1. State Grid Hunan Electric Power Company Limited Research Institute, Changsha 410007, Hunan, China
Abstract
In order to locate the single-phase-to-ground fault in distribution network, a research method of single-phase-to-ground fault location and recovery technology in distribution network is proposed. According to the characteristics of single-phase-to-ground fault in distribution network, the fault characteristics of zero-sequence current and three-phase current transient records are extracted by generalized S transform of correlation coefficient, and multi-source redundant information is formed. Fuzzy C-means clustering analysis method is used to fuse multiple fault features online location strategy. The simulation results show that the fuzzy clustering based on FCM changes continuously with the accumulation of samples, and the sample center changes with the enrichment of the samples. When the arc suppression coil is grounded with different initial phase angle transition resistance and intermittent fault, the state of each measuring point can be correctly identified, and the accurate energization rate is 97%. The test results show that the system can achieve accurate positioning for all sections.
Funder
Science and Technology Project of State Grid
Subject
Electrical and Electronic Engineering,Energy Engineering and Power Technology,Modeling and Simulation