Assessment of operation of safety channel signal cables at nuclear power plants under fire conditions

Author:

Lebedchenko O. S.1ORCID,Zykov V. I.1ORCID,Puzach S. V.1ORCID

Affiliation:

1. Academy of State Fire Service of Emercom of Russia

Abstract

Introduction. Signal cables of safety systems, installed at nuclear power plants (NPPs), retain the ability to conduct modulated signals during the time period needed to switch the reactor facility to a safe mode. However, the ability of signal cables to transmit signals correctly in the high temperature gas medium, which is typical for the early stage of a room fi re, has not been exposed to research.Aims and objectives. The co-authors offer a theoretical assessment of the ability of NPP safety system cables to correctly transmit modulated electric signals if exposed to fi re and current loads. The theoretical research into the temperature of the conductor of a signal cable at the initial stage of fi re has been performed towards this end.Theoretical background. The steady state heat conduction equation, describing heat transmission from the cable core to the environment through the cylinder-shaped insulation layer, is used to measure the temperature of the cable strand.Results and discussion. Temperature dependences describing the relation between the temperature of the conductor of a single - strand and single-wire cable KNEPng(А)-HF on the gas medium temperature are obtained. Relations between the temperature of the gas medium in the room on fi re and the current intensity in the electric cable (if the cable is laid vertically) are presented with account taken of the dependence between the specifi c resistance of the wire and the temperature if the maximal permissible operating temperature of cable strands is 70 °С, the maximal permissible operating temperature of cable strands in the overload operation mode is 80 °С, and the maximal cable strand heating temperature is equal to 160 °С when the short-circuit failure occurs. Maximal current intensity values are obtained for various operating modes in the condition of temperatures typical for the initial stage of an indoor fire, they allow to correctly conduct modulated signals within the time period needed to switch the reactor facility to a safe mode.Conclusions. The developed mathematical model and results of numerical experiments allow to assess the infl uence of the temperature in the room of a nuclear power plant in case of fi re on the ability of a signal cable of the safety system to transfer undistorted modulated signals depending on current loads and signal cable laying patterns (whether it is laid vertically or horizontally), and also to expand the range of the room temperature dependence on the current load provided in Electrical Installations Code (EIC).

Publisher

Moscow State University of Civil Engineering

Reference21 articles.

1. Meshchanov G.I., Kholodnyy S.D. Analysis of the combustion characteristics of polymer insulation of cables during their group laying. Cables and wires. 2010; 6(325):10-14. (rus.).

2. Khasanov I.R., Varlamkin A.A. Experimental methods for determining the fire resistance of cable penetrations in case of fire, taking into account the influence of load currents. Collection of materials: XVII All-Russian scientific-practical conference “Problems of predicting emergency situations”. Moscow, October 30–31, 2018 Moscow, FKU Center “Antistikha” Emercom of Russia, 2018; 77-78. (rus.).

3. Puzach S.V., Lebedchenko O.S. Mathematical modeling of the dynamics of hazardous fire factors during passive fire protection in the main buildings of nuclear power plants with water-cooled reactors: monograph. Moscow, Academy of the State Fire Service Emercom of Russia, 2019; 304. (rus.).

4. Titkov V.V., Dudkin S.M. Cable lines 6-10 kV and over. Influence of laying methods on temperature conditions. The News of Electrical Engineering. 2012; 3(75):2-4. URL: http://www.news.elteh.ru/arh/2012/75/10.php (rus.).

5. University complex as a regional center of education, science and culture: Materials of the All-Russian scientific and methodological conference. Orenburg, OSU Publ., 2018. URL: https://conference. osu.ru/archive/publications.html?detailed=14 (rus.).

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3