One of the main issues of improving the efficiency of air treatment in ventilation and air conditioning systems
(HVAC systems) is development of methodology for the realization of energy-efficient air treatment processes in the
contacting units. This paper investigates the thermodynamic models of “air-water” system, considering some features of
the transition area at the interface, including surface phases and boundary layers of air and water. It has a great impact on
the efficiency of processes of heat and moisture exchange in the contact units HVAC systems. The paper presents the
results of experimental studies to determine the air-water interfaces temperature when achieving a state of thermodynamic
balance condition in contacting media (air and water) in the working space of contact units. It was found that the
surface temperature is determined by state of the surface phase and depends on the direction process of heat and
moisture exchange (condensation or evaporation). The temperature factor k = Tdry/Ts as a criterion for determining the
effect of the state transition area on the processes of heat and moisture exchange, was used. Processing of results from
experimental researches in the processes of heat and mass transfer is presented in the form of criterial equations for Nu,
Nu. Results of the performed research are the basis for the formulation of theoretical ideas about the energy efficient
processes and the development of a new method for calculation of the contact units HVAC systems.