PREVENTION OF CAVITATION IN THE OPERATION OF WATER SUPPLY FACILITIES

Author:

Novokhatnii V.1ORCID,Usenko I.1ORCID,Sadovyi S.1ORCID,Gakh D.1ORCID

Affiliation:

1. National University “Yuri Kondratyuk Poltava Polytechnic”

Abstract

The article analyses the case of cavitation in centrifugal pumps of the 1st lift pumping station (PS-1) of the water supply system of one of the cities of Ukraine, supplied with water from a reservoir on the Dnipro River. In the classical scheme of a water supply system from a surface source, the operating mode of water treatment facilities should be uniform throughout the day, considering the water treatment’s physical and chemical processes. According to this, the operating mode of PS-1, which supplies ‘raw’ water to the water treatment plant, is considered uniform throughout the day. However, one caveat is that fast filters are washed with drinking water from clean water reservoirs. Its replenishment occurs due to the accelerated operation of the water treatment plant, and, at this time, PS-1 should increase the water supply to the water treatment plant. However, if the influx of water from the water intake structures is fixed, it occurs when the centrifugal pumps PS-1, operating under the bay, begin to capture some air. A two-phase flow of water forms in the pumps, which breaks away from the impeller blades, and cavitation occurs, destroying this impeller. It was necessary to establish the cause of cavitation and develop measures to eliminate it during the further operation of pumps at PS-1. The reasons for cavitation may be the following: failure of the operating point according to the Q–H characteristic at both low and high water flow rates; water flow breaks away from the blades with the formation of cavities and two-phase flow; violation of the requirement of the permissible cavitation reserve – the minimum pressure at the pump inlet if the pump is installed above the water level in the tank; violation of the requirement that there must always be more water at the pump inlet than at the outlet when installing the pump under the bay. The main reason for pump cavitation at PS-1 is the discrepancy between the water inflow from the water intake structures and the water supply regime to the water treatment facilities. The influx of water to PS-1 from the water intake structures is fixed, and the water use at the water treatment plant is uneven, as it depends on the technological process of water purification. The need to coordinate the modes of water supply into the suction pipeline of the pump and the mode of water supply to the pressure pipeline becomes urgent. In this case, there will be no cavitation. Keywords: water supply system, operating mode of facilities, 1st lift pumping station, cavitation.

Publisher

O.M.Beketov National University of Urban Economy in Kharkiv

Reference16 articles.

1. Abramov, M. M. (1982). Water supply: textbook (3rd ed.). Budvydav.

2. Khoruzhyi, P. D., Khomutetska, T. P., & Khoruzhyi, V. P. (2008). Resource-saving water supply technologies. Ahrarna nauka. https://drive.google.com/file/d/1wV7fzjFwFHtKvk0Z6bCrsPXftLA4jIFE/view [in Ukrainian]

3. Tkachuk, O. A. (2008). Improvement of water supply and distribution systems in settlements: monograph. NUVHP [in Ukrainian]

4. Novokhatnii, V. H. (2014). Water supply. Systems and networks: study guide. PoltNTU [in Ukrainian]

5. Khomutetska, T. P. (2016). Energy-saving water supply. Ahrarna nauka. https://drive.google.com/file/d/1b_vKTlfxmsWoSbNE8WJHCAdZG4xkJbWF/view [in Ukrainian]

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3