External Leakage Current Separation to Determine Arrester Condition Due to Contamination

Author:

Novizon Novizon,Mondrizal Mondrizal,Darwison Darwison,Aulia Aulia,Uldira Septiyeni Tesya

Abstract

Leakage current measurements can be used to determine the aging condition of the ZnO arrester. The leakage current that occurs in the arrester is divided into two, namely external and internal leakage currents. The external leakage current is affected by contamination and the internal leakage current is affected by the aging of the varistor in the arrester. The external and internal leakage currents are measured separately to determine their contribution to the arrester condition. In this study, the effect of salt contamination on the arrester was studied further. The level of contamination used consisted of low, medium and heavy. The obtained leakage current is analyzed using wavelet energy. The results of this study indicate that the wavelet energy of each leakage current is different and can be used as an indicator in further analysis. The conclusion obtained is that the external leakage current is affected by contamination and has a different energy with the internal leakage current due to aging of the varistor arrester components.

Publisher

Universitas Andalas

Subject

Marketing,Economics and Econometrics,General Materials Science,General Chemical Engineering

Reference23 articles.

1. Vid Vonˇcina, Jože Pihler, and Miro Milanoviˇ, “Extracting the Resistive Current Component from a Surge Arrester’s Leakage Current without Voltage Reference,” Sensors 2021, 21, 1257. https://doi.org/10.3390/s21041257. https://www.mdpi.com/journal/sensors.

2. Amir Hesam Khavari, Abdullah Munir, Zulkurnain Abdul-Malek, “Circuit-Based Method For Extracting The Resistive Leakage Current Of Metal Oxide Surge Arrester,” Journal homepage: http://beei.org. Bulletin of Electrical Engineering and Informatics. Vol. 9, No. 6, December 2020, pp. 2213~2221. ISSN: 2302-9285, DOI: 10.11591/EEEI.v9i6.2258.

3. Peningkatan Faktor Penuaan Arester Tanpa Sela Isolasi Polymer Akibat Kontaminan Kalsium Karbonat

4. A. Dlamini, P. Bokoro and W. Doorsamy, “The Effect Of Thermal Transient On The Leakage Current Of Metal Oxide Arresters,” 978-1-7281-4162-6/20/$31.00 ©2020 IEEE.

5. Erena Rosetta Puspitaningtyas, Sapto Nisworo, Agung Trihasto, "Predictions of the Remaining Life of the Main Transformer ZnO Arresters Based on Corrective Resistive Leakage Current Measurements Using the Polynomial Regression Method," Proceedings of the National Seminar on Applied Technology Research: 2020.