Study on Impact of Gap Difference on Plasma Distribution of Direct Current Vacuum Circuit Breaker with Double-Break

Author:

Huang Chongyang1,Yin Yongshuai1,Liu Shuxin1,Du Hanwen2,Shan Zengyu3,Cao Yundong1

Affiliation:

1. Shenyang University of Technology

2. Shenyang Power Supply Company of State Grid Liaoning Electric Power Co., Ltd

3. Chifeng Power Supply Company of State Grid Mongolia Electric Power Co., Ltd

Abstract

Abstract During the fault current breaking process of a mechanical direct current vacuum circuit breaker (DC VCB) with double-break (DB), the mechanism's dispersion can result in a gap difference between the two breaks. A DB DC VCB breaking experiment platform is constructed in order to investigate the impact of gap difference on plasma distribution during the DB DC VCB breaking process. During the experiment, a high-speed camera is used to capture the vacuum arcing process at the two breaks under varying gap difference conditions. Then, the arc feature parameters and their variations during the zero zone process are extracted using image processing techniques, and the distribution patterns of plasma and arc energy at the two breaks are analyzed and compared. When there is no gap difference between the two breaks of the experimental DB DC VCB, there are no significant differences in arc energy and the sizes of high, medium, and low-temperature plasma zones between the two breaks. When there is a gap difference between two breaks, the break with the smaller gap has larger high and medium-temperature plasma zones, more concentrated arc energy, higher particle concentration, lower arc diffusion velocity and arc energy decay velocity, and a greater amount of residual plasma after the extinguishing of the arc. When the gap difference exceeds a certain threshold, energy spots appear on the contact surfaces, and a high concentration corridor of residual particles remains between the contacts after the current crosses zero, forming a breakdown weak point that eventually leads to arc re-ignition (hence interruption failure) under the action of transient recovery voltage (TRV).

Publisher

Research Square Platform LLC

Reference25 articles.

1. Wandi, Z. Zhiyuan, H. Pengzhi, L. et al. Modular Cascaded Multi-port DC Circuit Breaker for DC Grid Application. Proceedings of the CSEE. 43(11), 4355–4366(2023).

2. Daochun, H. Huaqing, W. Wanlin, Q. et al. Voltage Sharing Design of Series Multi-break Mechanical Switch Considering the Whole Structure of Hybrid DC Circuit Breaker. Proceedings of the CSEE.42(6), 2407–2415(2022).

3. Liang,G. Xiaoguang,W. Wandi, Z.et al. Equivalent Evaluation Standard and Scheme Design for Breaking Test of Hybrid HVDC Circuit Breaker. Proceedings of the CSEE.41(4),1485–1495 + 1553(2021).

4. Dielectric strength and statistical property of single and triple-break vacuum interrupters in series.IEEE Transactions on Dielectrics and Electrical Insulation;Minfu L,2007

5. Investigations on the HVDC vacuum circuit breaker based on intelligent models;Jiyan Z;Transactions of China Electrotechnical Society,2015