Partial discharge fault identification of transformer based on CNN-SVM and multi-model fusion

Author:

An Qi,Yang Panshuo,Wang Kepeng,Han Xiaohui,An Guoqing,Du Zhenbin,He Ping

Abstract

Abstract Partial discharge pattern recognition has been established as a standard diagnostic tool for monitoring the operation of electrical equipment. Intelligent state recognition is the development trend of transformer state recognition, but the existing intelligent state recognition has the disadvantages of single model and low recognition accuracy. In order to overcome this shortcoming, a multi-dimensional information source transformer partial discharge fault identification method based on D-S evidence theory is proposed. Firstly, wavelet packet decomposition is used to extract the energy features of high frequency partial discharge signal and ultrasonic signal. Then, according to the selected feature set, the convolutional neural network (CNN) model and CNN-SVM model are established respectively. Finally, the Dempster-Shafer(D-S) evidence theory is used to combine the output results of the two signal recognition models. The results show that using the proposed wavelet packet decomposition energy feature set as input vector, the recognition rates of the two signals CNN-SVM models reach 95% and 81.67%, which are 3.33% and 8.34% higher than CNN respectively. The overall performance of D-S evidence theory fusion method is better than that of CNN and CNN-SVM, and the accuracy and consistency are improved by 3.33% and 16.66% respectively. The effectiveness and feasibility of this method are verified.

Publisher

Research Square Platform LLC

Reference24 articles.

1. "Overview and Partial Discharge Analysis of Power Transformers: A Literature Review," in IEEE Access;Hussain MR,2021

2. "Application of improved Hilbert-Huang transform to partial discharge signal analysis,";Gu F-C;IEEE Transactions on Dielectrics and Electrical Insulation,2018

3. C. Xiang, Z. Huang, J. Li, Q. Zhou and W. Yao, "Graphic approaches for faults diagnosis for Camellia insulating liquid filled transformers based on dissolved gas analysis," in IEEE Transactions on Dielectrics and Electrical Insulation, vol. 25, no. 5, pp. 1897–1903, Oct. 2018.M. Duval, A review of faults detectable by gas-in-oil analysis in transformers. IEEE Electr. Insul. M. 2002, 18(3):8–17.

4. Zhang Yi, Zhu Yongli. Partial Discharge pattern Recognition Method by combining Graph Signal and Graph Convolutional Network [J]. Proceedings of the CSEE,2021,41(18):6472–6481.

5. Multi-dimensional source partial discharge fault identification based on CNN + D-S evidence theory [J];WANG Lei Zhang;Electric Power Engineering Technology,2022

Cited by 1 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3