Thermal performance analysis and optimization design of dry type air core reactor with the double rain cover

Author:

Yuan Fa1,Yang Shou2,Qin Shi3,Lv Kai2,Tang Bo2,Han Shan4

Affiliation:

1. College of Electrical Engineering and New Energy, China Three Gorges University, Yichang, China + Hubei Provincial Engineering Technology Research Center for Power Transmission-Line, China Three Gorges University, Yichang, China

2. College of Electrical Engineering and New Energy, China Three Gorges University, Yichang, China

3. School of Electrical Engineering and Information, Wuhan Institute of Technology, Wuhan, China

4. Medical College, China Three Gorges University, Yichang, China

Abstract

In this paper, a fluid-thermal coupled finite element model is established according to the design parameters of dry type air core reactor. The detailed temperature distribution can be achieved, the maximum error coefficient of temperature rise is only 6% compared with the test results of prototype, and the accuracy of finite element calculate method is verified. Taking the equal height and heat flux design parameters of reactor as research object, the natural-convection cooling performance of reactor with and without the rain cover is investigated. It can be found that the temperature rise of reactor is significantly increased when adding the rain cover, and the reasons are given by analyzing the fluid velocity distribution of air ducts between the encapsulation coils. In order to reduce the temperature rise of the reactor with the rain cover, the optimization method based on the orthogonal experiment design and finite element method is proposed. The six factors of the double rain cover are given, which mainly affect the temperature rise of reactor, and the five levels are selected, the influence curve and contribution rate of each factor on the temperature rise of reactor are analyzed. The results show that the contribution ratio of the parameter H1, L1, and L2, are obviously higher than the parameter H2, L3, and ?, so the more attention should be paid in the design of double rain cover. Meanwhile, the optimal structural parameters of rain cover are given based on the influence curves, and the temperature rise is only 43.25?. The results show that the optimization method can reduce the temperature rise of reactor significantly. In addition, the temperature distribution of inner encapsulations coils of reactor are basically the same, the current carrying capacity of coils can be fully utilized, which provides an important guidance for the optimization design of reactor.

Publisher

National Library of Serbia

Subject

Renewable Energy, Sustainability and the Environment

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3