Based on the simulation results of the typical rural ultra-low energy
building (ULEB) in 5 different climatic regions of China, three indicative
technical parameters for paralleled-loop exhaust air heat pump (PEAHP) R&D-
which are nominal heating/cooling capacity, maximum required fresh air to
return air ratio (MFRR) and system energy efficiency grades- were calculated
and summarized according to the demand of indoor thermal comforts by using
statistic method. The nominal heating/cooling capacities were determined
according to the peak loads, which are 6.84/2.01kW, 5/2.96 kW, 3.9/4.6 kW,
3.08/5.02 kW and 3.4/0.46 kW in the ULEB of Harbin, Beijing, Shanghai,
Guangzhou and Kunming respectively. To ensure both thermal comforts and
energy conservation, during the heating season, full fresh air supply is
suggested in Beijing and the 1:0.5 MFRR is suggested in Harbin, Shanghai,
Guangzhou and Kunming. During the cooling season, the 1:5 MFRR is suggested
in Shanghai and Guangzhou, the 1:3, 1:1.5 and 1:0.5 MFRR are suggested in
Harbin, Beijing and Kunming respectively. The PEAHP energy efficiency grades
1~5 are 7.92~11.7, 7.58~11.5, 7.5~11.35, 6.12~9.27 and 4.64~7.03 during the
heating season of Harbin, Beijing, Shanghai, Guangzhou and Kunming
respectively, and are 2.33~3.54, 3.93~5.96, 4.61~6.98, 4.62~6.99 and
2.04~3.1 for the cooling season respectively.