Affiliation:
1. Faculty of Agriculture, Novi Sad
2. University Business Academy, Faculty for Economics and Engineering Management, Novi Sad
Abstract
This study reviews test results of the combustion of square soybean straw
bales used as fuel in manually fed boiler with nominal thermal power of 120
kWth. The influence of the mass flow rate (180, 265, 350, 435, and 520 kg
h-1) of inlet air and flue gas recirculation (0%, 16.5%, and 33%) fed to the
boiler furnace was continuously monitored. Direct method was used for
determination of the boiler thermal power. Correlation between boiler thermal
power and bale residence time has been observed and simple empirical equation
has been derived. General conclusions are as follows: the increase of the
flow rate of inlet air passing through the boiler furnace results in decrease
of the bale residence time and increase of the boiler thermal power. Share of
the flue gas recirculation of 16.5% increases bale residence time and
decreases average boiler thermal power in all regimes except in the regime
with inlet air flow rate of 265 kg h-1. In regime with 0% flue gas
recirculation boiler thermal power was higher than nominal in regimes with
435 and 520 kg h-1 inlet air flow rates. In regimes having inlet air mass
flow rate of 350 kg h-1 boiler thermal power is equal to the nominal power of
120 kWth.