Affiliation:
1. North China Electric Power University, School of Control and Computer Engineering, State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, Beijing, China
Abstract
When searching for the optimum condenser cooling water flow in a thermal
power plant with natural draft cooling towers, it is essential to evaluate
the outlet water temperature of cooling towers when the cooling water flow
and inlet water temperature change. However, the air outlet temperature and
tower draft or inlet air velocity are strongly coupled for natural draft
cooling towers. Traditional methods, such as trial and error method, graphic
method and iterative methods are not simple and efficient enough to be used
for plant practice. In this paper, we combine Merkel equation with draft
equation, and develop the coupled description for performance evaluation of
natural draft cooling towers. This model contains two inputs: the cooling
water flow, the inlet cooling water temperature and two outputs: the outlet
water temperature, the inlet air velocity, equivalent to tower draft. In this
model, we furthermore put forward a soft-sensing algorithm to calculate the
total drag coefficient instead of empirical correlations. Finally, we design
an iterative approach to solve this coupling model, and illustrate three
cases to prove that the coupling model and solving approach proposed in our
paper are effective for cooling tower performance evaluation.