AbstractLine‐to‐line short circuits are the transient disturbances that cause the highest currents as well as the largest voltage imbalances in inverter‐based microgrids. This paper presents a control scheme for grid‐forming inverters in islanded microgrids that limits the current to a safe value during these types of short circuits while providing a lower voltage imbalance compared to state‐of‐the‐art current limiting techniques. This control scheme is based on reducing both the amplitude of the reference voltage with the maximum amplitude of the reference current and the instantaneous reference voltage with only the inductive component of the virtual impedance. The combination of these two control actions provides low voltage imbalance, as the theoretical and experimental studies reveal. This voltage imbalance improvement is the main contribution of this paper and is maintained when the microgrid supplies linear and non‐linear loads. In the theoretical study, the paper includes control design guidelines to satisfy static and dynamic specifications. The theoretical predictions are validated by means of experimental results measured in a laboratory microgrid. A practical performance comparison of current limiting techniques based on experimental tests is also reported.