Affiliation:
1. School of Mechanical Engineering and Automation Shanghai University Shanghai China
2. School of Electrical Engineering Shanghai University of Electric Power Shanghai China
3. State Grid Lishui Liandu Power Supply Company Lishui China
4. State Grid Shanghai Pudong Electric Power Supply Company Shanghai China
Abstract
AbstractSince compact high temperature superconducting (HTS) transformer has a small size and high efficiency, it can meet the requirements of high‐voltage transformers for vehicle‐mounted mobile substation. However, due to the small internal insulation size of the compact HTS transformers, it is necessary to improve the insulation strength to ensure the insulation safety of the transformer. Reasonable main insulation structure can greatly improve the insulation level of transformer. Based on the design theory of main insulation structure, this paper designs a main insulation structure model “small liquid nitrogen gap—barrier” suitable for compact HTS transformer. The insulation withstand voltage experiment of the main insulation structure shows that when the liquid nitrogen gap distance is less than 8 mm, the insulation strength of liquid nitrogen in the structure is improved. When the liquid nitrogen gap distance is too small, the size and thickness of the barrier will affect the insulation strength of the structure. According to the insulation strength of main insulation structures with different liquid nitrogen gaps, the feasibility of “small liquid nitrogen gap—barrier” main insulation structure is verified. The small liquid nitrogen gap structure can be adopted for the main insulation of compact HTS transformer.
Publisher
Institution of Engineering and Technology (IET)