Affiliation:
1. Electrical Engineering National Chin‐Yi University of Technology Taiping Dist. Taichung Taiwan
Abstract
AbstractPartial discharge (PD) detection is used to evaluate the insulation status of high‐voltage equipment. The most challenging aspect of traditional PD recognition is extracting features from the discharge signal. Accordingly, this study applied the visual geometry group‐19 (VGG‐19) model to gas‐insulated switchgear (GIS) PD image recognition. A high frequency current transformer and an LDP‐5 inductive sensor measured PD electrical signals emitted by 15‐kV GIS. Next, the Hilbert energy spectrum was obtained by Hilbert transform in the time and frequency domains. Compared with a phase‐resolved PD pattern, the Hilbert spectrum can represent the energy and instantaneous frequency with the time variable. Finally, the VGG‐19 model was applied for PD pattern recognition. For validation, its recognition performance was compared with that of a fractal theory by using a neural network method. The VGG‐19 method is straightforward and has a high PD recognition rate, thereby enabling equipment manufacturers to quickly verify the insulation of GIS during assembly or operation.
Funder
Ministry of Science and Technology, Taiwan
Publisher
Institution of Engineering and Technology (IET)
Subject
Electrical and Electronic Engineering,Atomic and Molecular Physics, and Optics
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献