An extended impedance‐based fault location algorithm in power distribution system with distributed generation using synchrophasors
-
Published:2023-12-15
Issue:3
Volume:18
Page:479-490
-
ISSN:1751-8687
-
Container-title:IET Generation, Transmission & Distribution
-
language:en
-
Short-container-title:IET Generation Trans & Dist
Author:
Chandran Sandhya1ORCID,
Gokaraju Ramakrishna1ORCID,
Narendra Krish2
Affiliation:
1. Electrical and Computer Engineering University of Saskatchewan, 57 Campus dr Saskatoon Saskatchewan Canada
2. Electric Power Group Pasadena California USA
Abstract
AbstractAccurately locating power distribution faults reduces the total outage duration and provides better system reliability. Fault location using the traditional impedance‐based method may be very challenging in an active distribution system. However, taking into consideration the ease of implementation and cost effectiveness, a novel impedance‐based method is proposed to locate the fault by using the highly accurate time‐synchronized voltage and current phasors obtained from distribution phasor measurement units. The synchrophasor measurements obtained from the substation and various feeder segments are used in a two‐step algorithm based on the apparent impedance calculation to locate the exact source of the event. The algorithm uses phasor estimates to first identify the faulted feeder sub‐region and later uses measurements from a remote end device to eliminate pseudo‐faulted points to obtain the actual fault location. The effectiveness of the proposed method is realized using IEEE 34 bus system. Based on different fault types simulated at various parts of the system, the algorithm accurately estimates fault location in the range of ±1% of the line length. The proposed method is effective in locating faults for any type of network and topologies, with as many or as few (minimum 2) phasor measurement units in the system.
Publisher
Institution of Engineering and Technology (IET)
Subject
Electrical and Electronic Engineering,Energy Engineering and Power Technology,Control and Systems Engineering
Reference29 articles.
1. Fault Location in Power Distribution System With Penetration of Distributed Generation
2. IEC/IEEE.60255.118.1.:IEEE/IEC international standard–measuring relays and protection equipment–part 118‐1: Synchrophasor for power systems–measurements.IEEE Piscataway NJ(2018)
3. Das R.:Determining the locations of faults in distribution systems. In:Sixth International Conference on Developments in Power System Protection (Conf. Publ. No. 434) pp.188–191.IEEE Piscataway NJ(1998)
4. C37.114.2014:IEEE guide for determining fault location on ac transmission and distribution lines.IEEE Std C37‐114‐2014 (Revision of IEEE Std C37‐114‐2004) pp.1–76.IEEE Piscataway NJ(2015)
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献