Affiliation:
1. Energy Management Research Center University of Mohaghegh Ardabili Ardabil Iran
2. Faculty of Electronics, Communication and Computers University of Pitesti Pitesti Romania
3. Doctoral School Polytechnic University of Bucharest Bucharest Romania
4. ICSI Energy, National Research and Development Institute for Cryogenic and Isotopic Technologies Ramnicu Valcea Romania
Abstract
AbstractModern electrical power system design will increase renewable energy sources (RES) dominance. Rotating masses, the main source of inertia in power systems, have been greatly decreased in renewable energy producing systems. Thus, load–frequency equilibrium is an important indicator of these systems' performance and safety. This work introduces a fractional‐order (FO) operator‐based cascade control structure for islanded microgrid (μG) load‐frequency control (LFC). The structure utilizes a tilt–FO derivative with filter (TFODn) in the first level to reduce noise. The second level implements the proportional integral (PI) controller's FO form (FOPI), making it a tilt–FO derivative with a filter cascaded to the FOPI controller (TOFDn‐FOPI). The optimal controller parameters for quick dynamic responses with low frequency fluctuation are determined using a unique cost function and prairie dog optimization (PDO) algorithm. The LFC control loops have frequency deviation‐based responsive loads (RL). Control signal delays, RES output changes, parameter uncertainties, and cyber vandalism are examined. Laboratory‐scale tests also assessed the controller's practicality. The proposed controller outperforms standard and FO type proportional integral derivative (PID) and PD‐PI controllers. The TFODn‐FOPI controller is suitable for complicated closed‐loop systems like islanded μGs due to its faster error clearing, reduced RL capacity, and superior time and frequency domain indicators.
Publisher
Institution of Engineering and Technology (IET)
Subject
Electrical and Electronic Engineering,Energy Engineering and Power Technology,Control and Systems Engineering
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献