Affiliation:
1. College of Electrical and Information Engineering Engineering Hunan University Changsha Hunan China
2. TBEA Hengyang Transformer Co., Ltd. Hengyang Hunan China
Abstract
AbstractThe extra‐high voltage (EHV) transformer winding disks are subjected to dynamic electromagnetic forces caused by short‐circuit currents. These periodically decaying impact forces may endanger the safety of the transformer. The winding constraint conditions around the circumference are different due to the influence of axial pressure structures and magnetic boundaries. Moreover, this difference becomes more evident as the voltage and capacity increase. To investigate the spatial differences and time effects of EHV transformer short‐circuit faults, this paper proposes a reliability evaluation method based on dynamic relative displacement (DRDEM) for the first time. Firstly, the suitable and efficient analysis method is summarized by comparing the deviation among different calculated impedances and the measured value. Then, the space‐time effect of windings is obtained by the static magnetic field and dynamic structural field based on equivalent compression supports. Furthermore, a 50 MVA/110 kV transformer is designed for the destructive short‐circuit test to simulate the short‐circuit ability feature of the EHV transformer. The disassembly phenomena after all the tests indicate that the DRDEM is more adaptable in characterizing the winding ability to withstand short circuit when investigating the spatial differences and time effects.
Funder
National Natural Science Foundation of China
Publisher
Institution of Engineering and Technology (IET)
Subject
Electrical and Electronic Engineering,Energy Engineering and Power Technology,Control and Systems Engineering
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献