Abstract
This work considers the dynamic modeling and simulation of a DC hybrid power system for a rural base transceiver station in Nigeria currently being powered by an AC diesel generator (DG). The transient behaviour of the system is studied under varying solar irradiation to ascertain the stability of the power supplied to the sensitive telecommunication equipment. Each component of the system is designed and simulated in a MATLAB/Simulink environment and connected to form the whole system. A permanent Magnet DC diesel generator is used as back-up power for the system. A detailed presentation of the solar array, buck converter, battery storage system, battery controller, diesel generator and the load are presented in this paper. The result shows a stable power output to the load at rated voltage of 48 V.
Publisher
European Open Access Publishing (Europa Publishing)
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献
1. Sizing and dynamic modeling a Hybrid Renewable Power System for Paradise River, NL, Canada;2022 IEEE 13th Annual Ubiquitous Computing, Electronics & Mobile Communication Conference (UEMCON);2022-10-26
2. Low-Cost Open Source IoT-Based SCADA System for a BTS Site Using ESP32 and Arduino IoT Cloud;2021 IEEE 12th Annual Ubiquitous Computing, Electronics & Mobile Communication Conference (UEMCON);2021-12-01