Cooperation of a three-phase transformer with non-linear load

Author:

Daniluk Mateusz1,Drabek Tomasz1,Lerch Tomasz1

Affiliation:

1. AGH Akademia Górniczo-Hutnicza, al. Mickiewicza 30, 30-059 Kraków, Polska

Abstract

The paper presents the theoretical basics and the derivation of the American standard expression used to determine the thermally permissible current of three-phase dry transformers with nonlinear loads. The results of the measurement verification of this expression are presented, with different shapes of loading currents of the dry transformers under test. The results of the tests confirmed the correctness of the expression for contemporary transformers only.

Publisher

University of Applied Sciences in Tarnow, Poland

Reference13 articles.

1. IEEE STANDARD C57.110-2008, IEEE Recommended Practice for Establishing Liquid-Filled and Dry-Type Power and Distribution Transformer Capability When Supplying Nonsinusoidal Load Currents, 2008.

2. Carpinelli G, Caramaa P, Di Vito E, Losi A, Verde P, Probabilistic Evaluation of the Economical Damage due to Harmonic Losses in Industrial Energy System, IEEE Transactions on Power Delivery, 1996; 11: 1021–1031.

3. IEEE STANDARD C27.1920.

4. Rak J, Gała M, Jagieła K, Kępiński M, Analiza obciążenia i strat w transformatorach przekształtnikowych układów napędowych, Zeszyty Problemowe – Maszyny Elektryczne, Nr 89/2011.

5. Jayasinghe NR, Lucas JR, Perera KBIM, Power System Harmonic Effects on Distribution Transformer and New Design considerations for K Factor transformers, IEEE Sri Lanka Annual Sessions, September 2003.