Abstract
Abstract
The micron metal particles are inevitably produced in long-term operation condition of high voltage direct current SF6 insulated apparatus, which could frequently cause the surface discharge. Degradation of long-term surface discharge will be a severe threat to the insulation strength. Aiming at this problem, the surface charge accumulation and flashover voltage of epoxy itself before and after discharge degradation by particles were compared in this paper. The composition after degradation was measured by EDS and FTIR. The microstructure was observed by SEM. The roughness was measured as well. The trap distribution was measured by SPD. The mechanism of degradation and its effect on insulation characteristics were analyzed. The results show that the surface charge accumulation increase three times after degradation. Additionally, flashover voltage decreases 19% after degradation. The smoothly surface after degradation decrease the trap energy level for 14%, which might be the change reason of surface charge accumulation and flashover voltage. This paper can offer as a reference for the effect of micron metal particles on insulation degradation in SF6 gas insulated equipment.
Funder
Science and Technology Project of China Huaneng Group Co.,Ltd.
Subject
Surfaces, Coatings and Films,Acoustics and Ultrasonics,Condensed Matter Physics,Electronic, Optical and Magnetic Materials
Cited by
10 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献