Author:
Chen Hao,Fang Wenxuan,Han Kuo,Qiao Xin
Abstract
Abstract
Grounding grid plays an important role in protection of main device for power system. With the increase of power capacity and voltage level, the safety of grounding grid is particularly important. In this paper, the seriously corroded flat steel of grounding grid in 220kV substation was investigated by means of different test methods. The result showed that electrode potentials difference existed between different locations on the surface of the buried grounding electrode was the major reason to cause electrochemical corrosion. Meanwhile, higher sulphur and chlorine content of the soil around the substation caused by long-term industrial pollution, led to rapid depletion of zinc coating and acceleration of corrosion process of grounding material. Additionally, effective suggestions were presented in order to reduce the grounding resistance and improve the anti-corrosion performance.
Reference15 articles.
1. Corrosion and protection of materials for grounding grid;Ding;Corrosion Science and Protection Technology,2019
2. Research Progresses in the corrosion and protection of grounding grid at substation;Lv;Total Corrosion Control,2013
3. Corrosion behavior of copper-clad steel bars with unclad two-end faces for grounding grids in the red clay soil;Shao;Journal of Materials Engineering and Performance,2017
4. Simulated corrosion test of Q235 steel in diatomite soil;Li;Journal of Iron and Steel Research International,2015
5. Corrosion performance of mild steel and galvanized iron in clay soil environment;Karthick;Arabian Journal of Chemistry,2020
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献