Author:
Almuhsen Tahseen Ali Abd,Sultan Ahmed Jasim
Abstract
Abstract
Protection relays play an important role in the power systems to maintain stability, reliability, selectivity, and security for the power systems. In this paper, genetic algorithm (GA) optimization technique with pilot protection (PP) and without pilot protection (WPP) has been used to obtain proper coordination and the optimum value of transmission lines protection relays between distance relays (DRs) and directional overcurrent relays (DOCRs), as well as the critical case for fails in high voltage circuit breaker (HVCB) during faults, so using breaker failure relays (BFRs) for IEEE-8 bus system. The main aim of the used PP to reduce the overall time of DOCRs. A comparison is made with previous work in literature to show the efficiency and accuracy of the proposed algorithm with PP and the total operation time of DOCRs in the network is minimized.
Reference29 articles.
1. Optimal computation of distance relays second zone timing in a mixed protection scheme with directional relays;Perez;IEEE Trans. on Power Delivery,2001
2. Optimal coordination of distance and directional overcurrent relays considering different network topologies;Damchi;Iranian Journal of Electrical\& Electronic Engineering,2015
3. Optimum coordination of directional overcurrent relays for combined overhead/cable distribution system with linear programming technique;Khond;Protection and Control of Modern Power Systems,2019
4. Advances in breaker-failure protection;Altuve,2006