Author:
Zhu Wenwei,Wang Xiangbing,Liang Aiwu,Zhao Yifeng,Fan Xinghui,Liu Gang
Abstract
Abstract
This paper describes changes on micro-structure and aggregation structure of cross-linked polyethylene (XLPE) with different thermal histories after different times of overheating treatment to analogize the short-term fault or emergency overload in actual operating cables. 5, 10 and 20 times overheating treatment were conducted on a spare cable and a retired cable with service years of 32, whose insulation were analyzed by the diagnostic measurements of Fourier transform infrared spectroscopy (FTIR), differential scanning calorimetry (DSC) and thermogravimetry (TG). The results show that the spare cable has presented a trend of improvement on the insulation properties after overheating treatment below 20 times, but slight deterioration occurs after 20 times overheating treatment; the retired cable with service years of 32 has presented a trend of degradation on the insulation properties at the first 5 times overheating treatment, and a severe deterioration occurs after 20 times overheating treatment.
Reference11 articles.
1. Thermal and mechanical properties analysis for EHV XLPE cables with different operating years;Luo,2013
2. Effect of Long-time Electrical and Thermal Stresses upon the Endurance Capability of Cable Insulation Material;Tzimas;IEEE Transactions on Dielectrics and Electrical Insulation,2009
3. Observations on Structural Changes under Thermal Ageing of Cross-linked Polyethylene Used As Power Cables Insulation;Boukezzi;Iranian Polymer Journal,2008
4. Structure morphology modification of cable insulation polymers;Campus,1998
5. Effect of Artificial Thermal Aging on the Crystallinity of XLPE Insulation Cables: X-ray Study;Boukezzi,2007
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献