Mozgova A S,Shchennikova T V
Abstract
Abstract
The article presents the findings of the tests conducted for the forced air heating unit of a supply ventilation system. The supply air system is designed to feed clean air into the industrial facility of the oil-gas field of the Yamalo-Nenets Autonomous District. The tests were performed in five modes at the ambient air temperatures of -5, -10, -15, -20, -25 °C. The mode throughout the tests was steady, i.e. the temperatures of water and air remained unchanged within 30 minutes before the tests. Since the capacity of the heater unit was proved to be 24 - 41.5% according to the test results, recommendations were made to improve the capacity. With the said measures having been taken, control measurements of test parameters were carried out, the actual U-value was calculated and the capacity of the heater unit was determined. The performed work is relevant in view of theoretical and practical significance for engineers and employees of industrial enterprises servicing the ventilation systems.
Reference20 articles.
1. Lighting products: problems of technical and legal regulation of saving and energy efficiency;Bakulina;Light & engineering,2018
2. Issues of implementing the state program of energy saving and energy efficiency;Borshcheniuk;E3S Web of Conferences,2019
3. Management models of efficiency of development of resource and energy saving systems using methods of approximation of step functions;Alabugin;Proceedings of the World Congress on Engineering,2017
4. Assessment of energy saving and energy efficiency development in Russia and abroad;Meshcheryakova;E3S Web of Conferences,2019
5. Issues of implementing the state program of energy saving and energy efficiency;Borshcheniuk;E3S Web of Conferences,2019
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献