Author:
Rajab A,Gumilang H,Tsuchie M,Kozako M,Hikita M,Suzuki T
Abstract
Abstract
The natural ester of tri-ester type has been implemented on a high voltage large power transformer, rated at 420 kV, since 2014. The high voltage transformer is known prone to the static electrification risk. Palm fatty acid ester (PFAE) which is a monoester oil type has also been tried on the high voltage power transformer. For a retrofilling purpose, some portion of the previously used insulating oil (it is mainly mineral oil) will remain in the transformer. It is then demanded to study the static electrification of a mixture of PFAE and mineral oil. This paper presents an investigation results on the static electrification properties of PFAE-mineral oil mixture at various percentage ratios of PFAE. The results show that charging tendency (ECT) increase with the percentage ratio of PFAE, but then decreases for the oil containing only PFAE. On the other side, the resistivity of oil mixtures decreases with the increase of percentage ratio of PFAE but then increases for the oil containing only PFAE.
Reference13 articles.
1. Study on Increase of Electrostatic Charging Tendency of Insulating Oil and the Diagnosis on Streaming Electrification;Tsuchie,1999
2. Diagnosis on Increase in Electrostatic Charging Tendency of Mineral Insulating Oil for Power Transformers due to Aging;Okabe;IEEE Trans. on Dielectr and Electr. Insul,2010
3. Investigation of Electrostatic Charging Mechanism in Aged Oil-immersed Transformers;Okabe;IEEE Trans. on Dielectr. And Electr. Insul,2010
4. Study on Influence of Oxidation on Static Electrification in Transformer Oil;Shima,2014