Author:
Lan Zhijun,Wang Yaping,Wu Jianling,Fan Yongqiang
Abstract
Abstract
This paper mainly presents typical solutions to disconnecting switch overheating and mechanical problems of power grid in Extra High Voltage (EHV). In recent years, many faults have happened in the EHV power grid due to overheating and mechanical problems of disconnecting switches in Inner Mongolia. Dust storm weather and the special structure are main reasons which induced disconnecting switch lower operation reliability. For the overheating problems, the solutions include using conducting metal belt, replacing material of knee-arm wheel and modifying the structure of rolling-contact assembly; for the mechanical problems, the solutions include using dust shield, renovating operating mechanism and decreasing mechanically-driven part. Meanwhile suggestions are proposed as well for the design and application of isolator in the power networks of Western Inner Mongolia and the Northwester China which have similarly peculiar natural environments.
Reference5 articles.
1. Research on BLDCM actuator intelligent control strategy of the HV disconnecting switch. C;Semedo,2014
2. Design of Temperature Measurement System for High Voltage Disconnecting Switch. C;Yuanyi,2014
3. Measurement depth effects on the apparent temperature sensitivity of soil respiration in field studies;Graf;J. Biogeosciences,2008
4. Apparent temperature anisotropies due to wave activity in the solar wind;Verscharen;J. Annales Geophysicae,2011
5. Why the disconnect Problems with a clamp style catheter connector;Ryan;J. Regional Anesthesia & Pain Medicine,2019
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献