Author:
Buryanina N S,Korolyuk Y F,Koryakina M L,Lesnykh E V,Suslov K V
Abstract
Abstract
In addition to periodic components of industrial frequency, the aperiodic ones arise in windings and on the generator output leads under the conditions of shortcuts. These aperiodic components slow down the operation of the main differential protection of a generator up to ten periods of a network frequency with the application of saturated magnetic cores of current transformers as well as zero current relays and transformer differential protection [1]. This slowing down promotes accidents and can even lead to generator’s winding and steel burn-out at high-ampere currents. The present paper considers the ways to reduce the impact of aperiodic components on the operation of digital relay protection of generators and generator-transformer blocks and proposes generator’s directional digital protection.
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献