Harmonics in current and voltage waveforms produced by nonlinear loads in a distribution system can be minimised using passive filters; however, implementing these filters requires the calculation of several suitable parameters for filter components. This work aimed to simulate and analyse the harmonics in the Al-Itihad 11 kV distribution system that branches off from Zubayr substation (33/11 kV) in Basra in Iraq using MATLAB/SIMULINK. Five non-linear loads were simulated to generate harmonics in the simulated Al-Itihad distribution system, and for each non-linear load three types of filters were tested: a single tuned filter (STF), double tuned filter (DTF), and C-type filter. The objectives of these filters to minimise the total harmonic distortion (THD) in the voltage and current waveforms, to minimise the total current, and to improve the power factor of the distribution system. The simulation results showed a reduction in total harmonic distortion, a reduction in the current at the main distribution feeder, and an improvement in the power factor of the feeder.
Reference15 articles.
1. Reduction In Harmonic Distortion Of The System Using Active Power Filter In Matlab/Simulink;Chaughule;International Journal of Computational Engineering Research,2013
2. Analysis of Harmonics and Harmonic Mitigation Methods in Distribution Systems;Davudi;Australian Journal of Basic and Applied Sciences,2011
3. Loop Frame of Reference Based Harmonic Power Flow for Unbalanced Radial Distribution Systems;Yang;Electrical Power and Energy Systems,2016
4. Review of harmonic analysis, modeling and mitigation techniques;Kalaira;Renewable and Sustainable Energy Reviews
5. Harmonic Analysis in Power Systems Due to Non Linear Loads;Kaushik,2014
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献