Author:
Wang Xiangbing,Liang Aiwu,Wang Yanfeng,Zhu Wenwei,Zhao Yifeng,Dai Xinyun,Fan Xinghui,Xie Yue,Liu Gang
Abstract
Abstract
In order to investigate the cross-linked polyethylene (XLPE) insulation characteristics of a retired high-voltage cable that has been in operation for 16 years and to evaluate the reliability of reusing it for practical operation, a 180-day pre-qualification test method was applied to a section of this cable to inspect the changes of aggregation structure. In this paper, the electric field and the thermal field of the inner, medium and outer positions of the insulation under the accelerated aging test were analyzed and converted to the corresponding equivalent condition at the surface of the conductor core. It can be found that equivalent testing conditions of the medium and outer positions are close to the cable practical operation condition. The diagnostic measurements of fourier transform infrared spectroscopy (FTIR), differential scanning calorimetry (DSC) and X-ray diffraction (X-ray) were conducted to analyse the aggregation structure of the samples. The results showed that the molecular chain of the inner position of the cable insulation was damaged and the crystalline structure was slightly degraded under high-strength test condition. On the contrary, the crystalline structure of medium and outer positions were both improved after the accelerated aging test because of the reduction of the impurities and the annealing effect. So it can be expected that the rest of this retired cables still have the potential to reuse in long-term actual operation condition.
Reference10 articles.
1. Structure morphology modification of cable insulation polymers;Campus,1998
2. Thermal and mechanical properties analysis for EHV XLPE cables with different operating years;Luo,2013
3. Test and Analysis of Insulation Deterioration of XLPE Power Cable;Wang;High Voltage Engineering Journal,2014
4. Investigation on insulation material morphological structure of 110 and 220 kV XLPE retired cables for reusing;Xu;IEEE Trans. Dielectr. Electr. Insul.,2014
5. Analysis on Aggregation Structure of Retired 110 kV XLPE Cables Insulation;Zhang;Insulating Materials Journal,2016