Author:
Zhao Cong,Li Suya,Li Songyuan,Li Nan,Guo Bowen,Yan Wei
Abstract
Abstract
The ferromagnetic resonance overvoltage and overcurrent can often appear in the neutral non-effective grounding system, which is caused by the electromagnetic voltage transformer saturation under a certain condition. At present, two different types of primary harmonic eliminators are mainly used to solve the ferromagnetic resonance, which are voltage-sensitive resistor type and thermal resistor type. In this paper, the simulation model based on ATP-EMTP program is established and the results of different harmonic eliminators are compared. The results prove that the primary harmonic eliminator of thermal resistor type can more effectively suppress the ferromagnetic resonance.