Author:
Zeng Wenhui,Liu Xiaoyu,Wang Hanyu,Li Chunmei,Sun Xu,Zhang Zhirong
Abstract
Abstract
As a key link of power transmission, substation main wiring plays an important role in improving the reliability of power supply in the grid. At present, the design of substation main wiring mainly is made with reference to the typical design schemes. However, due to the continuous development of load and the reliability requirements, the traditional wiring scheme may not fully meet the actual operation requirements. In response to this problem, a new main wiring idea is proposed, 3/2 circuit breaker wiring is added to the conventional double bus wiring scheme to form a mixed wiring scheme. The reliability of each scheme is calculated and analyzed. A certain 220kV substation with heavy load in Chengdu is taken as an example, the loss of social output value is considered, the comprehensive economy of the whole life cycle of the substation construction is calculated and compared, and finally the conclusion is drawn that the reliability and economy of the proposed scheme are the best.
Subject
General Physics and Astronomy
Reference13 articles.
1. Reliability evaluation of substation bus arrangements considering economical operation of transformer;Zhou;Journal of Electric Power Science and Technology,2011
2. Three-state models in power system reliability evaluations;Endrenyi;IEEE Transactions on Power Apparatus and Systems,1971
3. A computerized approach to substation and switching station reliability evaluation;Grover;IEEE Transactions on Power Apparatus and Systems,1974
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献