Author:
Li Mengjia,Jiang Ningqiang
Abstract
Abstract
Because of the complex structure, the variable-speed pumped storage (VSPS) unit would face more stability problems in operation compared with conventional generators in the power grid. To overcome the shortcomings of the PI controller, the fractional order PI (FOPI) controller is applied for VSPS in pumping mode. To compare the quality of the two controllers, the WSCC 9-bus system with VSPS is studied under different disturbances. The dynamic performance is evaluated by calculating the integral of time multiplied absolute error criterion (ITAE) of rotor speed and active power of the stator. The result shows that the FOPI control strategy can effectively improve the dynamic performance of VSPS.
Subject
Computer Science Applications,History,Education
Reference12 articles.
1. The contribution of wind-hydro pumped storage systems in meeting Turkey's electric energy demand
2. Advanced Vector Control Design for DFIM-Based Hydropower Storage for Fault Ride-Through Enhancement
3. Analytical studies on power system dynamic stability enhancement by doubly-fed adjustable speed machine [C];Koyanagi;International Conference on Power System Technology, Australia: IEEE.