Abstract
Abstract
With the correct choice of the arrester by voltage class and compliance with the calculated protective distance without taking into account the propagation velocity of the current wave on the grounding grid, overvoltages exceeding discharge or residual voltage may occur on the protected equipment, in particular the transformer. Thus, when calculating the installation of the arrester that protects the substation from incoming lightning surges from a transmission lines, it is necessary to take into account the propagation of the current wave on the grounding grid. The propagation velocity of electromagnetic waves in a 150 kV substations grounding grid was measured. The measured wave propagation velocities are in the range of 50–100⋅106 m/s. Thus, the obtained velocity of wave propagation on the grounding grid used in service is several times less than the speed of light. The measured value correlates well with similar experiments conducted for buried conductors located in soils with similar parameters and the results of mathematical modeling for a grounding grid having similar dimensions and mesh size.