Fast reserve supply input systems significantly increase the reliability of power supply due to the possibility of preserving the technological process in case of emergency situations. The accuracy of determining the phase of the residual voltage on the busbar in process of connecting the power reserve supply provides a way to significantly reduce the starting overcurrents. In this paper, some modifications of the annealing method for determining the phase of the residual voltage on main section of busbar for emergency mode are considered. The obtained simulation results based on MATLAB environment make it possible to carry out a comparative analysis of a number of calculations for phase estimation design of automatic transfer switch operations based on simulated annealing.