Group control of air-cooled gas apparatuses

Author:

Hoshimov U H,Ishnazarov O Kh

Abstract

Abstract The paper considers the possibility of reducing electric power consumption by aircooled gas apparatus of a gas compressor station. The authors propose a system with breakdown of ventilators into IV groups with five ventilators in each group. Comparison of operation modes of a traditional cooling system and a grouped one with fans speed regulation on the basis of a frequency converter showed that the grouped handling system saved up to 40% of electric power.

Publisher

IOP Publishing

Subject

General Physics and Astronomy

Reference10 articles.

1. Synthesis and analysis of electric drive units of compressor stations under stochastic perturbations;Kryukov;Electrotechnics,2013

2. A combined version of gas air cooling units on linear and booster compressor stations;Yanvarev;AIP Conference Proceedings,2018

3. Determination of energy efficiency of air-cooling units based on apparatuses with different number of fans;Krupnikov;Omskiy Nauchniy Vestnik,2015

4. Adaptive automatic control system for air-cooled gas apparatus;Abakumov;J. Phys.: Conf. Ser.,2018

5. Mathematical modeling of electric consumption of the gas cooling process;Ishnazarov;E3S Web of Conferences,2021