Electrical environment can be altered at 1 km distances from high voltage power lines.

Author:

Matthews James C,Wright Matthew D,Buckley Alison J,Henshaw Denis L,Shallcross Dudley E

Abstract

Abstract High voltage powerlines emit electrical charges into the atmosphere which can then attach to aerosols. This space charge above ground can be measured directly using ion spectrometers or indirectly through perturbations of the Earth’s potential gradient using field mills. Several publications are reviewed to find evidence of aerosol charging at a distance from power lines. Field measurements of charge state near to high voltage power lines selected due to their high emissions of ions measured a small positive enhancement of electrical charge on aerosols at distances greater than 300 m, corresponding to a transit time of up to 400 s A quasi one-dimensional model of ion-aerosol interactions from a high voltage powerlines found that the addition of new ions to an aerosol population will result in those ions transferring charge to the aerosol which would then remain the dominant carrier of charge several hundred meters downwind. 10-min PG measurements from a fixed site measuring in 2008 compared measurements when the site was downwind of a 275 kV powerline to times with no wind and found evidence of space charge overhead through greater fields and variability at distances over 800 m These studies combined show evidence that the electrical environment near to power lines can be altered beyond 1 km from AC high voltage power lines, with excess charges likely to be concentrated on aerosol.

Publisher

IOP Publishing

Reference44 articles.

1. Challenges in coupling atmospheric electricity with biological systems;Hunting;Int. J. Biometeorol,2021

2. Proximity to overhead power lines and childhood leukaemia: an international pooled analysis;Amoon;Br. J. Cancer,2018

3. Air ion mobility spectra and concentrations upwind and downwind of overhead AC high voltage power lines Atmos;Wright;Environ,2014

4. Corona ion induced atmospheric potential gradient perturbations near high voltage power lines Atmos. Res. 44(39) 5093-5100 [5] Hendrickson R C 1986 Space charge drift from a +/− 400-kV direct current transmission line Bioelectromagnetics;Matthews,2010

5. Corona ions from high-voltage power lines: Nature of emission and dispersion;Jayaratne;J. Electrostat,2011