Author:
Zolińska K,Mirek P,Panowski M
Abstract
Abstract
The paper analyses the feasibility of determining the parameters of a heat exchanger operating in the crop production and realising low-temperature heat recovery from biological processes. For the first time, the Flownex 8.7 Simulation Environment has been used for this purpose. The temperature of the waste water was between 20 and 30°C. On the basis of the simulations, the power of the heat exchanger is determined to be 1 MW. The heat exchanger can efficiently heat up cold water from a deep well (7-10°C) to an assumed temperature of 19.7°C. The results from the simulation calculations correspond to the results obtained under actual conditions within a range of up to 2%.