Author:
Zheng J,Chiva J,Castro J,Liu Y,Oliva A
Abstract
Abstract
LiBr/H2O as working pair in absorption chiller is widely used in the absorption refrigeration system, and the electrical conductivity is used as secondary properties as an empirical relation with temperature and concentration as a simple method to measure the concentration. In this paper, another working pair Carrol/H2O is chosen, more suitable for air-cooled cycles. Carrol contains ethylene glycol and LiBr with a mass ratio at 4.5:1 and has advantages of low risk of crystallization and reduce the LiBr charge. The working range for the LiBr/H2O solution is temperature 25-80°C, at concentration 50–64%, in term of Carrol/H2O system, the temperature range is 25-80°C, concentration range is 50%-75%. The electrical conductivity will be measured according to the working range and a typical used solution extracted from an absorption chiller prototype will also be measured to compare with the experimental result.
Subject
General Physics and Astronomy
Reference8 articles.
1. Evaluation of a small capacity, hot water driven, air-cooled H2O-LiBr absorption machine;Castro;Hvac & Research
2. Properties of Carrol system and a machine design for solar powered, air-cooled, absorption space cooling;Reiman,1981
3. Electrical conduction in liquids and solids;Semat,1958
4. Electrical conductivity of concentrated lithium bromide aqueous solutions;Frled;J. Chem. Eng. Data,1983
5. Modification of the falkenhagen equation to fit conduc-timetric data for concentrated electrolyte solutions;Diego;J. Electroanal. Chem.,1997
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献