Abstract
Abstract
Taking a 110 kV transmission line as the research object, a refined finite element model of three pole two line transmission tower line system is established.Considering collision and contact between a dropped wire and ground, nonlinear dynamic analyses of the system with different break points and different numbers of broken wires were performed. The results showed that the break point location has little effects on the impact action of broken wire; the tension decay coefficient of the broken wire decreases with increase in the height of the hanging point position, while that of the unbroken wire decreases first and then increases with increase in the height of the hanging point position. The initial pretension, wind direction angle and span of the cable are selected for parameter analysis. The influence of these parameters on the nonlinear dynamic stability critical load of the hollow mezzanine concrete pole line system is investigated.
Subject
General Physics and Astronomy
Reference7 articles.
1. Longitudinal loads from broken conductors and broken insulators and their effect on transmission lines [J];Peyrot;IEEE Transactions on Power Apparatus and Systems,1980
2. Broken wire tests on a model transmission line system[J];Mozer;IEEE Transactions on Power Apparatus and Systems,1981
3. Model test for icing line disconnection on a long span transmission tower-line system [J];Chuncheng;Journal of Vibration and Shock,2012
4. Experimental research for broken conductor wire of ± 800 kV DC EHV suspension tower model [J];Zeng lu;Electric Power Construction,2010
5. Broken wire analysis of transmission line systems[J];Siddiqui;Computer and Structures,1984