Author:
Suamir I N,Baliarta I N G,Arsana M E,Sudirman ,Sugina I M
Abstract
Abstract
This paper presents field analyses on the influences of condenser and evaporator approach temperatures of water cooled air conditioning system for a shopping mall. The mall building comprises food and non-food retail stores and uses a centralized air conditioning (AC) system to condition the entire building. The AC system comprises three chillers with the same cooling capacity. Chillers’ performance parameters included power consumption, condensing and evaporating temperatures, evaporator-condenser approach temperatures, pressure drop and cooling capacity parameters were hourly recorded for a period of one year. Performance characteristics of each chiller were evaluated at different condenser and evaporator approach temperatures and regression analyses were also established to examine the correlations and influences of the approach temperatures on the chillers’ performance. The analyses results showed that the increase of condenser approach temperature could increase the power consumption and reduce the coefficient of performance (COP) of the chillers. While evaporator approach temperature was found to have insignificant effect to the chiller performance. The results also showed that for the investigated chillers with condenser and evaporator approach temperatures maintained below 2 K, the approach temperatures had negligible correlation to the power consumption and the overall performance of the chillers. At this operational conditions, the water cooled air conditioning systems could operate at their best possible performance.
Subject
General Physics and Astronomy
Reference16 articles.
1. A review on buildings energy consumption information;Perez-Lombard;Energy Build,2008
2. Waste Heat Recovery from Central AC System for Hot Water Supply; A Case Study for Hotel Building Application in Indonesia;Suamir;Adv Sci Lett,2017
3. Integration of heat pump and heat recovery of central AC system for energy use reduction of hotel industry;Suamir,2015
4. Effects of Cooling Tower Performance to Water Cooled Chiller Energy Use: a Case Study toward Energy Conservation of Office Building;Suamir;International Conference on Applied Science and Technology (iCAST),2018
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献