Bao Zhenghong,Ren Jiyun,Wang Lili,Wang Shengjie,Chen Yao,Li Zibin,Wang Zile,Ma Yongfu,Li Liao,Chen Huan
Abstract
Abstract
Gas insulated switchgear (GIS) is a critical component in power system, and the insulation testing is crucial before putting it into operation. Despite passing AC withstand tests, some GIS equipment exhibit insulation faults during operation. Existing AC withstand tests fall short in detecting all insulation faults in GIS equipment. To address this issue, a proposal is made to conduct a comprehensive simulation of actual GIS equipment operating conditions through a combined voltage and current boost test, aiming to address the limitations of existing tests. This study, based on a 330kV GIS test platform, compares the partial discharge characteristics of suspension defects under traditional voltage-boosting mode and the combined voltage and current boost mode. The research investigates the influence of simultaneously applying voltage and current on discharge characteristics. It is observed that the voltage and current boost combined mode significantly increase the partial discharge inception voltage (PDIV) and the corresponding apparent discharge compared to other modes. The apparent discharge quantity after a certain period of current flow during the discharge development process is greater than that observed in other modes. The current notably enhances the ultrasonic amplitude of partial discharge. These findings establish an experimental foundation for conducting voltage and current combined boost tests in the field.
Reference10 articles.
1. Thirty-six years of service experience with a national population of gas-insulated substations;Istad;IEEE Transactions on Power Delivery. Norway,2010
2. Failure frequencies for high-voltage circuit breakers, disconnectors, earthing switches, instrument transtormers, and gas-insulated switchgear;Runde;IEEE Transactions on Peower Delivery. Norway,2013
3. Field impulse withstand test and partial discharge detection for ultra high voltage gas insulated switchgear equipment;Li;High Voltage Technology. China,2015
4. UHF Defect Evaluation in Gas Insulated Equipment;Meijer;IEEE Trans. Dielect. Elect. Insul.,2005
5. Analysis on a Floating Discharge Defect in GIS Disconnecting Switch;Li;High Voltage Apparatus. China,2015