The fault diagnosis method of winding deformation based on pulse coupling injection is becoming more and more popular due to its advantages of online detection. In order to further improve the method, a pulse generator with adjustable parameters is developed in this paper to provide stable excitation. Its amplitude is adjustable from 600v to 5000v, pulse width is adjustable from 100 to 1000ns, and frequency is adjustable from 1 to 20kHz. In the diagnosis of winding deformation, the current research mainly focuses on the single deformation fault, and rarely involves the mixed deformation fault. Therefore, based on the pulse coupling injection method, field experiments are carried out to verify the feasibility of the method and find out the important reasons affecting the curve. At the same time, the detection experiment of multi-winding deformation fault superposition of a transformer is carried out, and the RVM frequency divider is used to accurately diagnose the mixed fault types of transformer windings.
Reference9 articles.
1. Status and trends in transformer monitoring;Bengtsson;IEEE Transactions on Power Delivery,1996
2. The New Developed Health Index for Power Transformer Condition Assessment;Jian,2020
3. Online detection method for power transformer winding deformation and movement by impulse signal injection: Safety and feasibility validation;Zhao,2015
4. Transformer fault voicing recognition based on repeated Pattern Extraction and Gaussian Mixture Model [J];Wang;Guangdong Electric Power,2023
5. A deep learning based infrared image fault diagnosis method for power equipment [J];Chen;Guangdong Electric Power,2021