Abstract
Abstract
This paper aims to provide valuable insights and assistance for ensuring the safe operation of a 110 kV main transformer by conducting an in-depth analysis of tap changer breather oil leakage defects. By employing transformer testing, disassembly analysis, and other methods, this study successfully identifies and prevents the possibility of transformer failure. The analysis reveals that the deformation of the transformer winding is caused by insufficient short-circuit resistance, which leads to the deformation of the medium-voltage windings under the continuous action of electrodynamic forces during near-area short-circuit currents. Near-area short-circuits are a significant contributing factor to transformer failures. Therefore, it is recommended to enhance operation and maintenance management for older main transformers and optimize protection settings to reduce the risk of near-area short-circuit failures, thus ensuring the safe and stable operation of the main transformer.