Author:
Yu Bing,Yang Zhi,Lin Haofan,Jin Yongtao,Yang Yong
Abstract
Abstract
On-load tap-changer is widely used in current power systems. Its main function is to change the position of the transformer winding tap-connect when operating under transformer excitation or load. The on-load tap-changer is in the process of changing taps. In the middle, the resistor must be used to achieve the transition to limit the circulation during its transition. The structure of the on-load tap-changer can be divided into three parts, namely the switch, the tap selector and the operating mechanism. The complexity of the mechanism causes frequent failures of the on-load tap-changer. Through the analysis of the causes of multiple faults occurring on the on-load tap-changer of the transformer, the abnormal physical information of the on-load tap-changer before the fault occurs is discussed. A joint detection technique based on vibro-acoustic fingerprint and driving motor current (acoustic and electric) is proposed.
Reference13 articles.
1. New Solid-State on-Load Tap-Changer Topology for Distribution Transformers[J];Faiz;IEEE Power Engineering Review
2. A Static Alternative to the Transformer On-Load Tap-Changer[J];Arrillaga;IEEE Transactions on Power Apparatus & Systems, PAS-99
3. An assessment method for the reliability of on-load tap-changer of power transformer[J];Wang,2010
4. Loading Guide for Individual Transformers with On-load Tap-Changer Facility and the Comparison of Calculation Results with Established Loading Guide and the Consideration[J];Tojo;Ieej Transactions on Power & Energy,2004
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献