Author:
Felius L C,Hamdy M,Hrynyszyn B D,Dessen F
Abstract
Abstract
In this study, the energy savings and cost-effectiveness of building automation measures in a retrofitting context are evaluated for a Norwegian single-family house. In addition, two methods for calculating savings from implementing building automation control systems (BACS) are compared: energy performance simulation and the BACS factor method proposed in EN 15232. Four retrofitting packages and four automation levels are combined to create 16 model versions. This study shows that BACS can increase energy savings and improve indoor comfort when implemented as a retrofitting measure. However, the relative impact on energy savings of building automation decreases when the delivered energy is lower. In addition, the impact of building automation on the energy savings is low compared to the effect of retrofitting the building envelope. When only BACS are implemented, savings up to 21% can be achieved, but when an integrated solution is implemented savings up to 60% can be achieved. Finally, some directions for future work are suggested.
Cited by
8 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献