Abstract
Abstract
Aiming at the three-dimensional (3D) defects detection of high-voltage cables joint, a method based on iterative residual fitting is proposed. The 3D point cloud data was obtained by reconstructing the laser line projected onto the surface of the high-voltage cable joint. In order to remove noise generated by reconstruction which is located above or below the curve, a simple and effective strategy that the noise can be filtered by the gradient change in the neighborhood is adopted. Then a continuous iterative residual fitting method is proposed to effectively reduce the interference of the defect area on the curve fitting accuracy, thereby obtaining the accurate equation expression of the cable surface curve. By comparing the residual value of the high-voltage cable surface points relative to the fitting curve, the points of the defect area are marked. Finally 3D defect area is extracted through segmentation and clustering. Experiments have verified the effectiveness of the proposed method on artificial standard size defects and real manual ground defects. The absolute error of the depth (height) of artificial standard size defects is less than 0.05 mm. Compared with the traditional cylindrical fitting method, it can be seen that the recognition rate of the proposed method for manually ground defects of high-voltage cable joint is much higher than that of cylinder fitting method.
Funder
Natural Science Foundation
Guangzhou power supply bureau of Guangdong Power Grid Co.,Ltd
Subject
Applied Mathematics,Instrumentation,Engineering (miscellaneous)
Reference18 articles.
1. Fundamentals of partial discharge in the context of field cable testing;Boggs;IEEE Electr. Insul. Mag.,2000
2. Partial discharge characteristics of XLPE cable joint and interfacial phenomena with artificial defects;Arief,2008
3. Summary of different scale defect structures in XLPE cable insulation;Li;Insul. Mater.,2019
4. Semiconducting layer as an attractive PD detection sensor of XLPE cables;Vakilian;IEEE Trans. Dielectr. Electr. Insul. A,2006
5. Effective partial discharge measurement method for XLPE cables based on propagation characteristics of high frequency signal;Takahashi,2012
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献