Abstract
Abstract
Moist polluting substances on high-voltage insulator surfaces can cause power-line failures by triggering electric arcs. There are at present no effective methods of measuring insulator pollution levels during normal operations. In this work, we attempt to estimate insulator pollution leakage current (PLC) as an indirect method of measuring deposits in a 30 month period of simultaneously recording leakage current and related environmental variables in substation insulators. We analyzed the relationship between raw leakage current and environmental variables. We canceled out the influence of relative humidity on leakage current by adaptive filtering and then obtained the PLC by filtering out the anomalous peaks in the recording. The proposed method considerably reduces the correlation between leakage current and relative humidity (0.826 vs 0.019). The resulting signal was only slightly correlated with other environmental variables (<0.03), suggesting that the relationships between leakage current and temperature, wind direction and speed are mainly attributable to their influence on relative humidity. The PLC presents a quasi-annual smooth fluctuation over time with a magnitude similar to those obtained in laboratory tests. This novel technique could be used to monitor insulator PLC in real time and thus improve power supply continuity and reduce maintenance costs.
Subject
Applied Mathematics,Instrumentation,Engineering (miscellaneous)
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献