Author:
Sahu Prakash Chandra,Prusty Ramesh Chandra,Panda Sidhartha
Abstract
Purpose
The paper has proposed to implement gray wolf optimization (GWO)-based filter-type proportional derivative with (FPD) plus (1+ proportional integral) multistage controller in a three-area integrated source-type interlinked power network for achieving automatic generation control.
Design/methodology/approach
For analysis, a three area interconnected power system of which each area comprises three different generating units where thermal and hydro system as common. Micro sources like wind generator, diesel generator and gas unit are integrated with area1, area2 and area3 respectively. For realization of system nonlinearity some physical constraints like generation rate constraint, governor dead band and boiler dynamics are effected in the system.
Findings
The supremacy of multistage controller structure over simple proportional integral (PI), proportional integral, derivative (PID) and GWO technique over genetic algorithm, differential evolution techniques has been demonstrated. A comparison is made on performances of different controllers and sensitivity analysis on settling times, overshoots and undershoots of different dynamic responses of system as well as integral based error criteria subsequent a step load perturbation (SLP). Finally, sensitive analysis has been analyzed by varying size of SLP and network parameters in range ±50 per cent from its nominal value.
Originality/value
Design and implementation of a robust FPD plus (1 + PI) controller for AGC of nonlinear power system. The gains of the proposed controller are optimized by the application of GWO algorithm. An investigation has been done on the dynamic performances of the suggested system by conducting a comparative analysis with conventional PID controller tuned by various optimization techniques to verify its supremacy. Establishment of the robustness and sensitiveness of the controller by varying the size and position of the SLP, varying the loading of the system randomly and varying the time constants of the system.
Subject
Electrical and Electronic Engineering,Mechanical Engineering,Mechanics of Materials,Geotechnical Engineering and Engineering Geology,Civil and Structural Engineering
Reference20 articles.
1. Intelligent LFC concerning high penetration of wind power: synthesis and real-time application;IEEE Transactions on Sustainable Energy,2013
2. Dynamics of diesel and wind turbine generators on an isolated power system;Electrical Power and Energy Systems,1990
3. Comparison of performance of several cuckoo search algorithm based 2DOF controllers in AGC of multi-area thermal system;Electrical Power and Energy Systems,2014
4. Automatic generation control of multi area thermal system using bat algorithm optimized PD–PID Cascade controller;Electrical Power and Energy Systems,2015
5. Load frequency controller design via BAT algorithm for nonlinear interconnected power system;Electrical Power and Energy Systems,2016
Cited by
30 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献