Induced voltage analysis of superconducting fault current limiter
Author:
Wang Zhigao,Wang Shuhong,Qiu Jie,Gong Weizhi,Zhang Jingyin
Abstract
Purpose
– Saturated core type superconducting fault current limiter (SFCL) can effectively limit the short-circuit current in power system. However, the high induced voltage will occur between the terminals of DC superconducting bias winding caused by the variation of magnetic flux linked by DC winding due to the increasing short-circuit current. The DC source may be damaged. Thus, the induced voltage should be considered in DC winding design. The paper aims to discuss these issues.
Design/methodology/approach
– Three-dimensional finite element method coupled with electric circuit.
Findings
– The short-circuit current flowing through AC windings and induced voltage of DC winding are analyzed by using three-dimensional finite element method coupled with electric circuit for a 220-kV three-phase SFCL. Several circuit elements, such as a capacitor connected with DC winding in parallel, an additional short-circuit winding wound around DC core column and an energy-released piezoresistor, are, respectively, used for induced voltage reduction. These methods aim to save magnetic coupled energy in DC winding, or oppose the variation of magnetic flux, or limit the voltage of DC winding by using a resistor with low resistance.
Originality/value
– The different methods for reduction of induced voltage of superconducting DC winding are studied and discussed. The decreased induced voltage may benefit the safety of superconducting DC winding and the source.
Subject
Applied Mathematics,Electrical and Electronic Engineering,Computational Theory and Mathematics,Computer Science Applications
Reference7 articles.
1. Choe, Y.Y.
,
Lee, K.D.
and
Ryu, G.H.
(2001), “Study on the induced voltage according to the change of the winding turns”, International Conference on Electrical Machines and Systems, pp. 1-3. 2. Ruan, Q.T.
(2005), “Present situation of short circuit current control in Shanghai power grid and countermeasures”, Power System Technology, Vol. 29 No. 2, p. -. 3. Stemmle, M.
,
Neumann, C.
,
Merschel, F.
,
Schwing, U.
,
Weck, K.H.
,
Noe, M.
,
Breuer, F.
and
Elschner, S.
(2007), “Analysis of unsymmetrical faults in high voltage power systems with superconducting fault current limiters”, IEEE Transactions on Applied Superconductivity, Vol. 17 No. 2 Part 2, pp. 2347-2350. 4. Viana, W.C.
,
Micaleff, R.J.
and
Young, S.
(1999), “Transformer design consideration for mitigating geomagnetic induced saturation”, IEEE Transactions on Magnetics, Vol. 35 No. 5, pp. 3532-3534. 5. Wang, J.Z.
(2007), “Control system and experiments on a new type of saturated iron core”, Master's thesis, Taiyuan University of Technology, pp. 17-18.
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献
|
|